SolicitationArchivedFA466126R0010
Replace Substation Alpha Relay B11912 Amendment 0002
DEPT OF DEFENSE / DEPT OF THE AIR FORCE / FA4661 7 CONS CDKey dates?
- Posted?
- Sep 14, 2026
- Response deadline?
- Sep 18, 2026, 5:00 PM UTC
- Archive date?
- Oct 3, 2026
- Archive type?
- auto15
Classification?
- Notice type?
- Solicitation
- Base type?
- Solicitation
- Set-aside?
- Small Business Set Aside - Total
- Set-aside code?
- SBA
- PSC?
- J039
NAICS?
Issuing office?
- Department?
- DEPT OF DEFENSE
- Sub-tier?
- DEPT OF THE AIR FORCE
- Office?
- FA4661 7 CONS CD
- Office code?
- —
- Organization type?
- OFFICE
- Office address?
- DYESS AFB, TX, 79607-1581, USA
Place of performance?
- Street?
- —
- Street 2?
- —
- City?
- Dyess AFB
- State?
- TX
- Zip?
- 79607
- Country?
- USA
Contacts?
- Robert Albrightsonprimary
- Jesse T. Wisowatysecondary
Description?
The purpose of this amendment is to: 1. Attach the following documents related to contractor questions arising from the mandatory site visit: a) FA466126R0010 Q_A Final.pdf b) Dyess_AFB_Electrical_Study-Volume1 (Final Report)_Redacted.pdf c) Dyess_AFB, A-Sub Relay Settings.pdf d) Sub A Fdr A1 East Housing Relay.pdf e) Sub A Fdr A2 West Housing Relay.pdf 2. All other terms and conditions remain unchanged. This is a solicitation for the requirement of properly replacing the Substation Alpha Feeder Protection Relays at Building 11912 on Dyess AFB. The Contractor shall install (2) NEW GE 850 Feeder Protection Relays which are provided by the Government. The contractor shall install and wire in (2) new Feeder Protection Relays in accordance with NEC/ NETA standards. The Contractor shall program the (2) new Feeder protection relays to match programming of the previously installed GE 760 relays, via settings provided by the Electrical shop and test functionality without load. The Contractor shall coordinate with the Electrical shop prior to energizing the primary voltage for testing and commissioning. The Contractor shall commission and test the two new relays with full base load once installed with witnesses from Electrical, Contracting and R&O. The Contractor will coordinate with the Electrical Shop before conducting any power outages for acceptance tests if needed. Please see attachments for details.
Other notices in this solicitation?
- SolicitationReplace Substation Alpha Relay B11912 Amendment 0001Sep 14, 2026LATEST
- SolicitationReplace Substation Alpha Relay B11912Aug 25, 2026LATEST
Similar open contracts
Metadata?
- Notice ID?
- 4f509db3132e4b52b27d0744dd60ca39
- Full path?
- DEPT OF DEFENSE.DEPT OF THE AIR FORCE.FA4661 7 CONS CD
- Office code?
- —
- Ingested?
- Sep 29, 2026
- Updated?
- Sep 29, 2026