This notice has been superseded. See the latest notice: W065--Lease SPS Reverse Osmosis - Brooklyn & Manhattan (Award Notice)
SolicitationActive36C24226Q0560
W065--Lease SPS Reverse Osmosis - Brooklyn & Manhattan VAMC
VETERANS AFFAIRS, DEPARTMENT OF / VETERANS AFFAIRS, DEPARTMENT OF / 242-NETWORK CONTRACT OFFICE 02 (36C242)Key dates?
- Posted?
- Jun 4, 2026
- Response deadline?
- Jun 18, 2026, 6:00 PM UTC
- Archive date?
- —
- Archive type?
- autocustom
Classification?
- Notice type?
- Solicitation
- Base type?
- Solicitation
- Set-aside?
- —
- Set-aside code?
- —
- PSC?
- W065
NAICS?
Issuing office?
- Department?
- VETERANS AFFAIRS, DEPARTMENT OF
- Sub-tier?
- VETERANS AFFAIRS, DEPARTMENT OF
- Office?
- 242-NETWORK CONTRACT OFFICE 02 (36C242)
- Office code?
- 036.3600.36C242
- Organization type?
- OFFICE
- Office address?
- ALBANY, NY, 12208, USA
Place of performance?
- Street?
- —
- Street 2?
- —
- City?
- —
- State?
- —
- Zip?
- —
- Country?
- —
Contacts?
- Dolores Sachuk-ThompsonprimaryContract Specialist
Description?
TABLE 1: Water Quality Routine Testing Frequency for Critical Water, Utility Water, AER Final Rinse, and Steam Condensate for each (Brooklyn and Manhattan) of the Medical Centers will be: Water Quality Measurement Source Sampling Site(s) # of Samples per event Sampling Frequency # of Samples per year MANHATTAN & BROOKLYN pH Critical Water After the last treatment step at the water generation system At the point the distribution loop enters the processing area or first POU on the distribution loop 2 Monthly 24 Conductivity Critical Water At the point the distribution loop enters the processing area or first POU on the distribution loop 1 Monthly 12 Total Alkalinity Critical Water After the last treatment step, storage tanks At the point the distribution loop enters the processing area or first POU on the distribution loop 2 Monthly 24 Total Hardness Critical Water After the last treatment step At the point the distribution loop enters the processing area or first POU on the distribution loop 2 Monthly 24 BROOKLYN Bacteria Critical Water Loop out point Loop return point Each location of point-of-use in department (subject to change): Decon Sink Scope Sink Unity Ultrasonic Washer-Disinfector #1 Washer-Disinfector #2 7 Monthly 84 Endotoxin Critical Water Water storage tank Loop out point Loop return point Each location of point-of-use in department (subject to change): Decon Sink Scope Sink Unity Ultrasonic Washer-Disinfector #1 Washer-Disinfector #2 8 Monthly 96 MANHATTAN Bacteria Critical Water Loop out point Loop return point Each location of point-of-use in department (subject to change): Decon Sink #1 Decon Sink #2 Decon Sink #3 Decon Sink #4 Scope Sink #1 Scope Sink #2 Caviwave PRO Ultrasonic #1 Caviwave PRO Ultrasonic #2 Caviwave PRO Ultrasonic #3 Caviwave PRO Ultrasonic #4NY - will eventually have 4 ultrasonic Ok Washer-Disinfector #1 Washer-Disinfector #2 Washer-Disinfector #3 15 Monthly 156 Endotoxin Critical Water Water storage tank Loop out point Loop return point Each location of point-of-use in department (subject to change): Decon Sink #1 Decon Sink #2 Decon Sink #3 Decon Sink #4 Scope Sink #1 Scope Sink #2 Caviwave PRO Ultrasonic #1 Caviwave PRO Ultrasonic #2 Caviwave PRO Ultrasonic #3 Caviwave PRO Ultrasonic #4 Washer-Disinfector #1 Washer-Disinfector #2 Washer-Disinfector #3 16 Monthly 168 MANHATTAN & BROOKLYN Total Organic Carbon (TOC) Critical Water After the last treatment step At the point the distribution loop enters the processing area or first POU on the distribution loop 2 Quarterly 8 Ionic Contaminants Aluminum Chloride Copper Iron Manganese Nitrate Phosphate Sulfate Silicate Zinc Critical Water After the last treatment step At the point the distribution loop enters the processing area or first POU on the distribution loop 2 Quarterly 8 pH Utility Water At the point the distribution loop enters the processing area or first POU on the distribution loop 1 Quarterly 4 Conductivity Utility Water At the point the distribution loop enters the processing area or first POU on the distribution loop 1 Quarterly 4 Total Alkalinity Utility Water At the point the distribution loop enters the processing area or first POU on the distribution loop 1 Quarterly 4 Total Hardness Utility Water At the point the distribution loop enters the processing area or first POU on the distribution loop 1 Quarterly 4 BROOKLYN Bacteria Utility Water Each location of point-of-use in department (subject to change): Decon Sink Scope Sink Unity Ultrasonic Washer-Disinfector #1 Washer-Disinfector #2 5 Quarterly 20 MANHATTAN Bacteria Utility Water Each location of point-of-use in department (subject to change): Decon Sink #1 Decon Sink #2 Decon Sink #3 Decon Sink #4 Scope Sink #1 Scope Sink #2 Caviwave PRO Ultrasonic #1 Caviwave PRO Ultrasonic #2 Caviwave PRO Ultrasonic #3 Caviwave PRO Ultrasonic #4 Washer-Disinfector #1 Washer-Disinfector #2 Washer-Disinvector #3 13 Quarterly 44 Total Organic Carbon (TOC) Utility Water At the point the distribution loop enters the processing area or first POU on the distribution loop 1 Quarterly 4 Ionic Contaminants Aluminum Chloride Copper Iron Manganese Nitrate Phosphate Sulfate Silicate Zinc Utility Water At the point the distribution loop enters the processing area or first POU on the distribution loop 1 Quarterly 4 BROOKLYN pH Steam Steam Sterilizer Cooler Sample Port 1 Quarterly 4 Conductivity Steam Steam Sterilizer Cooler Sample Port 1 Quarterly 4 Total Alkalinity Steam Steam Sterilizer Cooler Sample Port 1 Quarterly 4 Total Hardness Steam Steam Sterilizer Cooler Sample Port 1 Quarterly 4 Ionic Contaminants Steam Steam Sterilizer Cooler Sample Port 1 Quarterly 4 Bacteria Automated Endoscope Reprocessor Medivator #27 Right Basin Medivator #27 Left Basin Medivator #28 Right Basin Medivator #28 Left Basin 4 Monthly 48 Endotoxin Automated Endoscope Reprocessor Medivator #27 Right Basin Medivator #27 Left Basin Medivator #28 Right Basin Medivator #28 Left Basin 4 Monthly 48 MANHATTAN pH Steam Steam Sterilizer Cooler Sample Port 2 Quarterly 8 Conductivity Steam Steam Sterilizer Cooler Sample Port 2 Quarterly 8 Total Alkalinity Steam Steam Sterilizer Cooler Sample Port 2 Quarterly 8 Total Hardness Steam Steam Sterilizer Cooler Sample Port 2 Quarterly 8 Ionic Contaminants Steam Steam Sterilizer Cooler Sample Port 2 Quarterly 8 Bacteria Automated Endoscope Reprocessor Medivators #1 Right Basin Medivators #1 Left Basin Medivators #2 Right Basin Medivators #2 Left Basin Medivators #3 Right Basin Medivators #3 Left Basin 6 Monthly 72 Endotoxin Automated Endoscope Reprocessor Medivators #1 Right Basin Medivators #1 Left Basin Medivators #2 Right Basin Medivators #2 Left Basin Medivators #3 Right Basin Medivators #3 Left Basin 6 Monthly 72
Attachments (3)?
Other notices in this solicitation?
- Award NoticeW065--Lease SPS Reverse Osmosis - Brooklyn & ManhattanJul 6, 2026LATEST
- SolicitationW065--Lease SPS Reverse Osmosis - Brooklyn & Manhattan VAMCJun 18, 2026
- SolicitationW065--Lease SPS Reverse Osmosis - Brooklyn & Manhattan VAMCJun 1, 2026
- PresolicitationW065--Lease SPS Reverse Osmosis - Brooklyn & Manhattan VAMCJun 1, 2026
- Sources SoughtW065--Lease/Service SPS Reverse Osmosis Brooklyn & Manhattan VAMCApr 23, 2026
Similar open contracts
Metadata?
- Notice ID?
- 26b816e0b5754310aeb701f44c9e49e5
- Full path?
- VETERANS AFFAIRS, DEPARTMENT OF.VETERANS AFFAIRS, DEPARTMENT OF.242-NETWORK CONTRACT OFFICE 02 (36C242)
- Office code?
- 036.3600.36C242
- Ingested?
- Jun 5, 2026
- Updated?
- Jul 11, 2026